Product Overview

The Apartment Module (AM) is a loop powered addressable device that helps reduce the costly consequences of an unwanted alarm. An occupant is able to silence a local audible warning, activated by a local smoke detector, and allowing a preset time to investigate the cause of the alarm. Local smoke detectors can be connected directly to the AM (conventional) or connected to the addressable loop (addressable) and assigned to the AM. Loop Powered Addressable Device Built-in short circuit isolation Hush facility Conventional zone input with heat/smoke detector sensing 100V Line Output with EOL monitoring Event logging of AM sequence at FACP Allows a group of detectors to be assigned to a nominated AM Aesthetically pleasing single gang wall plate – vertical or horizontal On board visual indication for “polling”, Fire and Fault status Remote ‘Hush’ button input terminals available Suitable for use on the FireFinder and LoopSense Fire Alarm Control Panels

Product Specification

Operating Voltage21 to 28 VDC (loop powered)

Quiescent Current


4.9mA with 6k2? EOL

1.9mA with 10?F EOL

Alarm Current4.2mA + Zone alarm current of 14.5mA

Zone Circuit


10 detectors (max) with 6k2? EOL (detector current < 1.2mA)

20 detectors (max) with 10?F EOL (detector current < 2.4mA)

 Zone EOL6k2?, 10?F
Speaker Circuit100Volt line, 6 W max, 47k EOL
Address Setting1 to 126
DimensionSingle gang PDL plate
MaterialHigh impact ABS (white)
Weight45 grams