The Zone Monitor with Isolator powers and controls the operation of a zone of up to 20 Apollo Series 65 or Orbis fire detectors from a Discovery or XP95 Loop. Loop powered. Visible LED. Built-in short circuit isolator
Product Specification
Voltage | 17-28vdc |
Quiescent current | 4mA + detector load |
Alarm current | 11mA at 24vdc |
EOL resistor value | 5.1k |
Maximum capacitor on zone terminals | 50?F |
Zone voltage | 19V ± 1V |
Operating temperature | -20°C to +70°C (no icing) |
Relative humidity | 0 to 95% (non condensing) |
IP Rating | IP54 |
Size | 150mm W x 90mm H x 48mm D |