Product Overview

The Ampac Single Zone Occupant Warning System is available as a 120 Watt audio output with an optional front panel control. The alert and evacuation signals are compliant to AS1670.1 and NZS4512 including voice messages as standard.
The speaker circuit is protected and monitored for shorts and interruptions. Up to three spur lines (branches) are supported. A monitored strobe output is provided as standard which supports both xenon and led strobes.
Each audio source (alert / evacuation signals, emergency paging and secondary analogue audio input) has a dedicated volume control.
Three programmable relays are provided, which default to Emergency Warning Condition, Fault and Test Mode.
The optional front panel control has an integrated emergency microphone (and can optionally support a hand held microphone)
The Single Zone Occupant Warning System is suitable for use in Ampac’s FireFinder and FireFinder Plus Fire Alarm Control Panels.

Product Specification

 120W
Supply Voltage     27VDC (nominal)
Max Audio Load120Watt
Quiescent Current (no audio load, no strobe load)240mAmps
Max. Current (full audio load, no strobe load)8Amps
Strobe Output (Xenon)8 sets (208-0011)
Strobe Output (LED)40 sets (4107-1005/6)
Audio output voltage100VAC
Temperature-20°C to 70°C
Humidity0-95% non-condensing
Alert / Evac Changeover time (secs)Alert only, Evac only, 60, 90, 120, 180, 300 or under manual control
Speaker EOLNominal 47k? 5% 1/3 Watt
THD<0.6%
Signal to Noise Ratio91dB

Amplifier Dimension

(L x W x H)

170mm x 210mm x 85mm