Product Overview

The XP95 Base Visual Alarm Device (VAD) incorporates a loop powered VAD with a standard intelligent mounting base and is used to signal a fire alarm in enclosed areas. The VAD self-test is achieved by means of an LED monitoring circuit. If the LEDs do not draw current when the VAD Base has been switched on a fault signal is transmitted when the device is next polled. Group addressing is a simple method of alerting an entire area or group of rooms without delay. For systems requiring isolators at every point the built-in isolator saves installation time and cost. The XP95 Base VAD can be used either with a detector fitted or with a cap for operation as a stand-alone alarm device and is moulded in polycarbonate with stainless steel contacts that accept solid or stranded cables of up to 2.5mm². Automatic LED check when VAD activated VAD flash rate of 0.5Hz Synchronised flash Individual & group addressing Built in short circuit isolator Complies with AS7240-23

Product Specification

Coverage Class

O

Flash Colour

White

Frequency Flash Rate

0.5Hz

Operating Voltage

17 to 28 V DC

Quiescent current

 300µA

Current operated

14mA

Dimensions

115mm x 30.5mm

Weight

156 grams

Operating temperature

-20° to +60°C

Humidity (no condensation)

0 to 95%

IP rating

21C

Approval

AS7240-23:2014