Product Overview

The Orbis IS Heat Detector monitors temperature by using a single thermistor network which provides a voltage output proportional to the external air temperature. There are seven classes of heat detectors in the Orbis IS range designed to suit a wide variety of operating conditions. Can be used for applications where smoke detectors are unsuitable. Ideal in environments that are dirty or smokey under normal conditions. Reduced incidences of false alarms. Increased reliability of detection. Approvals: EN54-5

Product Specification

Operating voltage14 to 28 VDC
Quiescent current80?A at 24 VDC
Size inc base100mm D x 50mm H
Operating temperature-40°C to +70°C (no icing)
Class T5: - 40°C to +40°C
Class T4: - 40°C to +60°C
Relative humidity0 to 98% (non condensing)
IP ratingIP23D (indoor use)
Weight70 grams (140g inc base)